CO₂ Sensor Placement
Where Should CO₂ Sensors Be Installed? A Practical Placement Guide
In areas where CO₂ is generated, or stored, then sensors should typically be installed low to the ground (around 12 - 16 inches) and as close as possible to potential leak sources such as gas cylinders or equipment.
Because carbon dioxide is more dense than air, it accumulates at low levels first. Correct positioning of the sensor ensures accurate readings, detecting leaks early, and improved safety before gas concentrations reach breathing height.
Why correct CO₂ sensor placement matters
Locating CO₂ sensors correctly is critical for effective early detection of hazardous gas levels and improves the safety of the environment.
If sensors are installed incorrectly then;
- leaks may not be detected early
- alarms may be delayed
- people in the location may be exposed to dangerous levels
CO₂ is particularly hazardous because:
- it cannot be seen or smelled
- it can build up unnoticed
- it settles in low-lying areas
How CO₂ behaves in the air
Understanding the behaviour of carbon dioxide is important in correctly installing the sensors because it:
- is more dense than air
- sinks and accumulates at low levels
- spreads outward from the source
This means the gas detection sensors must be positioned in those areas where the gas will accumulate first, rather than where people typically stand.
Common CO₂ sensor placement mistakes
The incorrect installation of CO₂ sensors is one of the biggest causes of detection failure and increased safety risks.
Common mistakes we typically see include:
- installing sensors at head height instead of low level
- placing sensors too far from gas sources
- installing only one sensor in large spaces
- positioning sensors near vents or airflow
- assuming one sensor covers multiple rooms
Recommended CO₂ sensor placement
1. Height
CO₂ sensors should be installed:
- approximately 12 to 16 inches above floor level
To enable CO₂ to be identified where its concentrations will rise first.
2. Distance from leak sources
Sensors should be installed close to the source of a potential leak, to quickly detect it:
- close to gas cylinders
- near valves and pipework
- close to the equipment which is using CO₂
3. Number of sensors required
Large or complex spaces may need multiple sensors to ensure the area is properly covered, but the exact number needed depends on:
- layout and size of the area
- number of gas sources
- ventilation
4. Ventilation considerations
Movement of air can dilute the concentration of carbon dioxide and therefore delay its detection, so you should avoid placing sensors:
- directly next to air vents or extraction systems
- in areas with strong airflow
Do you need both CO₂ and O₂ sensors?
In some environments, yes, and a dual or multi gas monitoring approach will provide full protection.
These situations include when gases such as nitrogen are also present because
- oxygen levels may decrease
- CO₂ levels may increase
So, in such instances
- CO₂ sensors detect toxicity
- O₂ sensors detect oxygen depletion
Typical installation locations by industry
Breweries and beverage production
- cellars
- CO₂ storage areas
- near drinks carbonation systems
Restaurants and hospitality
- back-of-house areas
- walk-in coolers
- gas storage rooms
Laboratories and medical facilities
- near incubators
- gas cylinder storage
- enclosed lab spaces
Dry ice storage
- storage rooms
- transport containers
- confined handling areas

Should I have or use fixed vs portable CO₂ monitoring
Fixed carbon dioxide monitoring systems
- continuously monitor specific and known troublesome areas
- are ideal for storage or production environments
Portable carbon dioxide monitors
- can be worn by personnel
- provide personal protection when moving between locations
A combination of both is recommended in most environments to provide maximum safety coverage.

Where should sensors be installed?
CO₂ sensors:
- low to the ground (CO₂ is more dense than air)
- near potential leak sources
O₂ sensors:
- at breathing height
- in areas where gas displacement may occur
The correct placement of the sensors is essential for reliable and accurate gas detection.
Common safety mistakes
Some of the most frequent safety issues include:
- using an oxygen monitor to detect CO₂
- assuming CO₂ can be detected by smell
- installing sensors in the wrong location
- not monitoring multi-gas environments properly
These mistakes can result in delayed detection and increased risk.

What is the recommended monitoring approach?
To ensure effective CO₂ detection, and correctly installing sensors is just as important as choosing the right sensors, it is recommended that:
- install sensors at low level
- position near gas sources
- use multiple sensors where required
- combine fixed and portable monitoring where appropriate
CO₂ Calculator
Many people believe an oxygen (O₂) monitor alone is enough to stay safe when using carbon dioxide (CO₂). In reality, CO₂ is a toxic gas, and dangerous levels can be reached long before O₂ alarms activate.
As CO₂ leaks into an area, it displaces oxygen. However, most O₂ monitors only alarm at around 19.5% O₂, by which point CO₂ concentrations may already be hazardous.
If your facility uses CO₂, a dedicated CO₂ monitor is essential. It provides earlier warning of leaks, helping protect people, reduce product loss, and minimise costly CO₂ waste.
Use this calculator to see how changing CO₂ levels affect the surrounding O₂ concentration.
SLOT Specified level of toxicity (1 - 5% of fatalities) SLOD Significant likelihood of death (50% fatalities)
Learn more about our CO₂ monitoring solutions or explore to find the right protection for your application.
FAQs
Why are CO₂ sensors installed low to the ground?
Because CO₂ is more dense than air and settles at low levels first.
Can CO₂ sensors be installed at head height?
No, they shouldn’t be installed at this level because this will delay detection as CO₂ accumulates at lower levels first.
How many CO₂ sensors do I need?
This will depend on the size and layout of the room and the number of gas sources there are in it. Generally, the larger, and more complicated the area, the greater the need for multiple sensors.
Should sensors be placed near ventilation systems?
No, they should never be placed near ventilation systems because the flow will dilute the concentration of the gas and delay its detection.
Key takeaway
Where CO₂ sensors are placed plays a key role in gas detection. Installing sensors at the correct height and location ensures early detection of leaks and helps protect people from potentially dangerous exposure.