Ax60+ Cultivate

Stay Safe and Cultivate

The Ax60+ Cultivate is the definitive solution for safeguarding indoor agriculture spaces, prioritizing CO₂ safety in settings like vertical farms, greenhouses, and cannabis cultivation facilities.

At the heart of this safety assurance lies our proprietary NDIR (non-dispersive infrared) sensor technology, harnessed by the Ax60+ Cultivate. This innovation guarantees precise CO₂ measurement, setting a new standard for reliability.

Designed for versatility, the monitor accommodates 1 to 4 sensors per system, with up to 4 alarm units per sensor. This flexibility ensures comprehensive coverage, adapting to the needs of extensive indoor grow operations.

Complementing its features, the Ax60+ Cultivate offers a 5-year warranty for sensors and electronics. It’s a dependable high-performance solution, assuring staff safety from potential CO₂ exposure risks. In the space of indoor agriculture, the Ax60+ Cultivate shines as a beacon of safety, precision, and dependability.

Key Features

  • Proprietary NDIR infrared CO₂ sensor with 40 second warmup time
  • Measurement range of 0-5% CO₂
  • Modular system supports 1-4 sensors and up to 4 alarm units per sensor
  • 5 year warranty on sensors and electronics
  • Available as quick connect plug and direct connect
  • Durable IP55 rated water-resistant enclosures
  • 24V power supply versions available for low voltage operation
  • Default preset but customizable alarm setpoints
  • Retrofits with existing Ax60+ systems

Information

Datasheets & Manuals

Installation

How should you install the Ax60+ unit for optimal safety monitoring, and where is the best location within your facility?

Legislations / Standards

The Ax60+ Cultivate caters to the intricate safety needs and regulations set by local, state, and federal authorities. Specifically optimised for indoor agriculture such as vertical farming, greenhouses and indoor cannabis farms, the Ax60+ Cultivate is finely tuned to adhere to rigorous USA standards such as OSHA, NBIC, NFPA, and IFC. This integration seamlessly complies with key USA regulations (NFPA 55, IFC, NBIC, OSHA, NIOSH), ensuring top-tier safety within the vertical farming domain.

Technical Specifications
FeatureSpecification
Gas DetectedCarbon Dioxide (CO2)
Sensor TechnologyNondispersive Infrared
Range0.1% to 5%
Default Alarm Set PointsUSA regulations (NFPA 55, IFC, NBIC, OSHA and NIOSH):
TWA - 5,000ppm (0.5%)
AL1 - 5,000ppm (0.5%)
AL2 - 15,000ppm (1.5%)
AL3 - 30,000ppm (3%)
Sensor Warm Up Time40 Seconds
Resolution0.01%
Accuracy±2.5% of the alarm levels
Response Time30 Seconds to T90
IP RatingIP55
LED IndicatorsGreen = Power
Red = Alarm
Warranty5 years for both sensor and electronics

Applications
  • Agriculture
  • Vertical Farming

Obsolete Product Manuals

Frequently Asked Questions

How to silence and acknowledge latched alarms on the Analox Ax60+

The Ax60+ systems have latched alarms as standard however does have the option of disabling alarm latching. It is our hope that the following information will help to avoid confusion when silencing and acknowledging alarms.

Latched Alarms

These will not clear unless acknowledged. For example, if the target gas level increases beyond the alarm threshold, the device will go into alarm and remain like this until the alarm has been acknowledged.

Non-Latched Alarms

These will clear without acknowledgement. For example, if the target gas level increases beyond the alarm threshold, the unit will go into alarm but once the gas returns to safe limits the alarm automatically clears.

Both Latched and Non-Latched alarms can be muted with a single press of the Accept/Test button, but in order to acknowledge a latched alarm the user must first cycle through the display until an ‘*’ is seen, then press and hold the Accept/Test button for 3 seconds (resulting in the ‘*’ changing into a ‘>’.

The video below shows an example of muting and acknowledging a latched alarm:

Can the Ax60+ Alarm Unit be mounted outside, and is it weather tight?

The Ax60+ Alarm/Strobe Unit is IP55 rated.

IP means Ingress Protection, the 2 numbers after indicate to what level the unit is able to protect itself against dust, moisture, liquids and accidental contact. The IP rating for this unit is broken down below;

  • 5 – Solids – Dust Protected. Limited ingress of dust permitted. Will not interfere with operation of the equipment. 2 to 8 hours.
  • 5 – Water – Protected against jets of water. Limited ingress permitted.

However, the unit is Not Waterproof/Weatherproof for long periods of time, and in direct sunlight the UV light will fade the label on the unit. The Alarm Unit can be mounted outside if it has sufficient protection from the elements.

How do I disable the Alarm sounders on the Ax60+?

There are two potential reasons for the Ax60+ to show a FLT16 code on the screen, these are:

  1. The sensor unit requires zero and span calibration adjustment (see the service manual for guidance on carrying out this process)
  2. The CO₂ sensor alarm directions have been incorrectly set.

If your unit is displaying a Flt16, first attempt a zero and span calibration adjustment then power cycle the device. If this is not possible or the issue is not resolved, check to see if it has been correctly configured as detailed below.

The Ax60+ is primarily a breathing air device, as such, the CO2 sensor unit alarms are restricted to only trigger in the ‘high-going’ direction. If a user changes the alarm ‘going’ to ‘low-going’ a FLT16 will ensue.

To clear this fault the following steps should be followed (be aware that only a short period of non-alarm time is available so you’ll need to be quick!!):

  1. Power cycle the Ax60+ (turn it off and on again)
  2. Wait for the sensors display on the screen
  3. Press the Accept/Test button briefly to silence any alarms. Press and hold the top two buttons (Cancel and cycle) until the top level menu is reached.
  4. Press the cycle button six times (until sensor config is shown)
  5. Press the Accept/Test button. Press the cycle button twice (Alarm direction is shown)Press the Accept/Test button. Select the sensor that had the alarm ‘going’
  6. changed (press cycle to move the arrow selector over until the relevant sensor is identified and press the Accept/. test button)
  7. Select the alarm that had the alarm ‘going’ changed
  8. (press cycle to move the arrow selector over until the relevant alarm is identified and press the Accept/test button)
  9. Change the alarm direction to ‘up’ (press the cycle button until the arrow selector points at the up arrow and press the Accept/test button)
  10. Press the cancel button five times until the sensors display on screen
  11. Acknowledge any faults displayed
  12. Power cycle the unit
How do I fix a loose RJ45 connector on my Analox Ax60+?

What should I do if my Ax60+ has a FLT16 on the display?

There are two potential reasons for the Ax60+ to show a FLT16 code on the screen, these are:

  1. The sensor unit requires zero and span calibration adjustment (see the service manual for guidance on carrying out this process)
  2. The CO₂ sensor alarm directions have been incorrectly set.

If your unit is displaying a Flt16, first attempt a zero and span calibration adjustment then power cycle the device. If this is not possible or the issue is not resolved, check to see if it has been correctly configured as detailed below.

The Ax60+ is primarily a breathing air device, as such, the CO₂ sensor unit alarms are restricted to only trigger in the ‘high-going’ direction. If a user changes the alarm ‘going’ to ‘low-going’ a FLT16 will ensue.

To clear this fault the following steps should be followed (be aware that only a short period of non-alarm time is available so you’ll need to be quick!!):

  1. Power cycle the Ax60+ (turn it off and on again)
  2. Wait for the sensors display on the screen
  3. Press the Accept/Test button briefly to silence any alarms. Press and hold the top two buttons (Cancel and cycle) until the top level menu is reached.
  4. Press the cycle button six times (until sensor config is shown)
  5. Press the Accept/Test button. Press the cycle button twice (Alarm direction is shown)Press the Accept/Test button. Select the sensor that had the alarm ‘going’
  6. changed (press cycle to move the arrow selector over until the relevant sensor is identified and press the Accept/. test button)
  7. Select the alarm that had the alarm ‘going’ changed
  8. (press cycle to move the arrow selector over until the relevant alarm is identified and press the Accept/test button)
  9. Change the alarm direction to ‘up’ (press the cycle button until the arrow selector points at the up arrow and press the Accept/test button)
  10. Press the cancel button five times until the sensors display on screen
  11. Acknowledge any faults displayed
  12. Power cycle the unit

Is the Ax60+ backwards compatible with the Ax60?

There is some backwards compatibility:

  • Ax60+ CO2 sensor units CAN be used with both Ax60 and Ax60+ central displays.
  • Ax60 sensor units CAN ONLY be used with Ax60 central displays.
  • Oxygen sensors CAN ONLY be used on the Ax60+ central displays.

See table below for reference:

 

Ax60 Central Display

Ax60+ Central Display

Ax60 CO2 Sensor

✔

✗

Ax60+ CO2 Sensor

✔

✔

Ax60+ O2 Sensor

✗

✔

What do I do if my Ax60+ Unit is in Alarm?

Stay out of the area, open all windows and doors to ventilate. Do not re-enter the area until the alarm condition stops and the reading on the display has returned to normal.

Have a suitably qualified person check the gas bottles/lines for leaks/frosting.

To silence the alarm, press the Accept/Test button.

Ax60+ Comms Fault

A COMMS fault means a sensor has developed a communications fault. May be caused by accidental cable disconnection. To clear a COMMS FAULT press Accept/Test to silence the buzzer then reconnect the cable.

A COMMS fault can also be caused by incorrect jumper positions. Each sensor must have a unique jumper position. Two sensors with the same jumper position will cause a COMMS fault.

  • Sensor 1 must have the jumper in position 1
  • Sensor 2 must have the jumper in position 2
  • Sensor 3 must have the jumper in position 3
  • Sensor 4 must have the jumper in position 4

Ax60+ Modular Gas Safety System

My Ax60+ is displaying FLT06

FLT06 is displayed when the Ax60+ fails to initialise correctly. This often means that the sensor did warm up correctly and did not reach its operating temperature. This can happen when the environment around the Ax60+ is too cold.

Turning the device off and on again should clear the FLT06.

If your device has latching faults enabled, the fault will need to be acknowledged first, to acknowledge the fault, please see the above instructions for acknowledging latched alarms.

My Ax60+ sensor unit got wet and won’t stop alarming

The Ax60+ sensor units are IP55 rated, which means they are water-resistant, but not waterproof.

If the Ax60+ sensor unit gets soaked, it can sometimes cause it to go into alarm in error.

Powering down the sensor unit and giving it time to dry out should solve the problem and the Ax60+ should return to normal operation.

What height should my Ax60+ sensors be installed?
  • CO₂ – 12-18″ above ground
  • Cultivate  – 12-18″ above ground
  • SAFE-OX – Average Head height
  • O₂ – Average Head height
  • CO – Average Head height